Isolation Flanges - NPT and Sweat Connections
  
  Overview
  
  
  
			
  Design Features
  The isolation flange is a combination of   a full port isolation ball valve and a companion flange for circulators. The   isolation flange allows easy service or replacement of the circulator without   the need to drain the system. 
    Free-floating flanges eliminate the need to   align flanges making the pump installation a snap. Includes capscrews and   nuts.
    Can be used with most circulators, including NRF/NBF/SSF wet rotors,   Series PL’s, Series 100, HV, PR & LR and other manufacturers’   pumps.
      Available Sizes:
   3/4", 1" & 1-1/4" (refer to dimension and weight   table for details).
  When closed, the isolation   flanges isolate the circulator from the rest of the system so the system does   not need to be drained when removing the circulator. 
  
  Operating Data
  
    - Maximum working pressure . . . . . . . 150 psi (10 bar)
 
    -  Maximum operating temperature . . . . .   250°F (121°C)
 
  
     Materials of Construction
    
    - Valve Body . . . . . . . . . . . . . . .   .  . . . . . . . . . . . . . Brass
 
    
    - Flange . . . . . . . . . . . . . . . . . .  . . . . . . Zinc   Plated Steel
    
 
    -  Ball . . . . . . .   . . . . . . . . . .   . . . . . . Chrome Plated Brass
    
 
    - Packing . . . . . . . . . . . . . . . .   . . . . . . . .  . . . . . . . Teflon
    
 
    - Seat Ring . . . . . . . . . . . . . . .   . . . . . . . . . . . .  . . . Teflon
    
 
    -  Stem . . . . . . . . . . . . . . . . . .   .. . . . . . . . . . . . . . . Brass
    
 
  
	
    Applications
    
      Brass and non-ferrous wetted inter-nal components make the isolation flanges   ideal for hydronic heating systems.
   
  Back To Top