Butt’s Pumps and Motors - page 1032

27
Refrigeration
Technical Specifications
High/ Medium Temperature Units 120 & 208/230V / 60Hz / 1 Ph
Condensing Unit
Part #
HP Volt
Appl.
LBP
Amps
(-10°F)
HBP
Amps
(+45°F)
LRA
Connections
Dimensions
Weight
Liq.
Suct.
L W H
59-UNE6181Eª
1/4+ 120 M/HBP -
7.05 38 1/4"
3/8"
18.5" 13.4" 11.9" 46 lbs
59-UNE6195E
1/3 120 M/HBP -
7.56 46 1/4"
3/8"
18.5" 13.4" 11.9" 46 lbs
59-UNE6195ECª
1/3 120 M/HBP -
7.56 46 1/4"
3/8"
18.5" 13.4" 11.9" 46 lbs
59-UT6217E1ª
1/2+ 120 M/HBP -
12.77 55 1/4"
3/8"
19.4" 16.3" 12.8" 68 lbs
59-UT6217E2
1/2+ 208/230 M/HBP -
12.77 55 1/4"
3/8"
19.4" 16.3" 12.8" 68 lbs
59-UT6220E1
3/4 120 M/HBP -
14.20 65 1/2"
1/4"
19.4" 16.3" 12.8" 70 lbs
59-UT6220E2
3/4 208/230 M/HBP -
14.20 65 1/2"
1/4"
19.4" 16.3" 12.8" 70 lbs
59-UJ9226E2
1 208/230 M/HBP -
16.50 72 1/4"
3/8"
20.1" 16.3" 15.4" 83 lbs
ª Does not include receiver or fan guard.
R22 Air Cooled Condensing Units
BTU Rating Conditions
Temperature LBP HBP
Ambient
90°F 90°F
Sub Cooling
5°F 5°F
Return Gas
40°F 65°F
Performance Capacity
High/ Medium Temperature Units 120 & 208/230V / 60Hz / 1 Ph
Condensing Unit
Part #
HP Volt
Appl.
BTU / Hour
-20°F -10°F 0°F +5°F +10°F +20°F +30°F +45°F +50°F
59-UNE6181Eª
1/4+ 120 M/HBP -
-
-
-
1400 1790 2328 3378 3589
59-UNE6195E
1/3 120 M/HBP -
-
-
-
1558 2000 2515 3743 3956
59-UNE6195ECª
1/3 120 M/HBP -
-
-
-
1558 2000 2515 3743 3956
59-UT6217E1ª
1/2+ 120 M/HBP -
-
-
-
2200 3100 4550 6449 7162
59-UT6217E2
1/2+ 208/230 M/HBP -
-
-
-
2200 3100 4550 6449 7162
59-UT6220E1
3/4 120 M/HBP -
-
-
-
4250 5500 6938 8889 9609
59-UT6220E2
3/4 208/230 M/HBP -
-
-
-
4250 5500 6938 8889 9609
59-UJ9226E2
1 208/230 M/HBP -
-
-
-
4500 5800 7494 10322 11465
ª Does not include receiver or fan guard.
Commercial
Refrigeration
59-UNE
Series Illustrated
Condensing Units
1...,1022,1023,1024,1025,1026,1027,1028,1029,1030,1031 1033,1034,1035,1036,1037,1038,1039,1040,1041,1042,...1665